Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
231
Minimum signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Set minimum point
of actual value
pump curve for
temperature sensor.
Fig. 85:
Minimum signal/value assignment, actual value sensor
Max. signal/value assignment
Analogue input (AI2)
Signal value
Corresponding value
Set maximum point
of actual value
pump curve for
temperature sensor.
Fig. 86:
Maximum signal/value assignment, actual value sensor
Data input is complete, once the minimum and maximum characteristic curve support
points have been entered.
NOTICE
If the signal type PT1000 has been selected, it’s possible to set a temperature cor-
rection value for the measured temperature. With this the electrical resistance of a
long sensor cable can be compensated.
In the “Settings” menu
, select
1.
“External interfaces”
2.
“Function analogue input AI1” ... “Function analogue input AI4”
3.
“Temperature correction” and set correction value (offset).
NOTICE
Optionally specify the position of the sensor for better understanding of the con-
nected sensor’s function.
This configured position does not influence the function or sensor use.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......