Faults, causes and remedies
254
WILO SE 2021-12
Code
Warning
Cause
Remedy
575
Remote control not
possible by radio.
The Bluetooth radio
module is faulty.
Software update is recom-
mended.
Contact Service.
Additional information
about causes and rem-
edy:
Pump function not im-
paired.
If a software update
does not eliminate the
issue, contact Service.
577
Software update can-
celled.
The software update
was not completed.
Software update with new
software bundle is recom-
mended.
Additional information
about causes and rem-
edy:
Software update was
not carried out; pump
continues to operate
with previous software
version.
578
HMI faulty.
A fault in the display
and operating unit
has been identified.
Replace display and oper-
ating unit.
Additional information
about causes and rem-
edy:
The display and operat-
ing unit is available as a
spare part.
579
HMI software not com-
patible.
Display and operating
unit cannot commu-
nicate correctly with
the pump.
Software update is recom-
mended.
Additional information
about causes and rem-
edy:
Pump function not im-
paired.
If a software update
does not eliminate the
issue, contact Service.
580
Too many wrong PIN
entries.
Too many connection
attempts with wrong
PIN.
Disconnect power supply
from the pump and switch
it on again.
Additional information
about causes and rem-
edies:
An incorrect PIN has
been entered more than
5 times.
For safety reasons, fur-
ther connection at-
tempts are prevented
without a restart.
582
Twin-head pump is not
compatible.
Twin-head pump
partner is not com-
patible with this
pump.
Select/install appropriate
twin-head pump partner.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......