Communication interfaces: Setting and function
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
233
In the “Settings” menu
, select
1.
“External interfaces”
2.
“Wilo Net setting”
3.
“Wilo Net address” and assign each pump its own address (1 ... 21).
Twin-head pump example
ƒ
Pump head left (l)
–
Wilo Net termination: ON
–
Wilo Net address: 1
ƒ
Pump head right (II)
–
Wilo Net termination: ON
–
Wilo Net address: 2
Example with Multi-Flow Adaptation featuring four pumps
ƒ
Primary pump
–
Wilo Net termination: ON
–
Wilo Net address: 1
ƒ
Pump secondary 1
–
Wilo Net termination: OFF
–
Wilo Net address: 2
ƒ
Pump secondary 2
–
Wilo Net termination: OFF
–
Wilo Net address: 3
ƒ
Pump secondary 3
–
Wilo Net termination: ON
–
Wilo Net address: 4
NOTICE
If a Multi-Flow Adaptation system is made up of twin-head pumps, this means a
maximum of 5 twin-head pumps can communicate with each other via Wilo Net in
the MFA network. In addition to this maximum of 5 twin-head pumps, up to 10 addi-
tional single pumps can be included in the network.
Other examples
The primary pump of a Multi-Flow Adaptation system is a twin-head pump and the
whole system should be able to be remotely monitored via a gateway.
ƒ
Primary twin-head pump = 2 participants (e.g. ID 1 and ID 2)
ƒ
Wilo-Smart Gateway = 1 participant (e.g. ID 21)
A maximum of 18 pumps remain on the secondary side in the MFA system (ID 3 ... 20).
In the Wilo Net settings, the Wilo Net ID address space of 1 ... 126 is displayed as ad-
justable.
However, only the ID address space of 1 ... 21 is available for a functioning Wilo Net
connection between pumps and accessories. A maximum of 21 participants can there-
fore communicate in Wilo Net.
Higher IDs mean that Wilo Net participants with higher IDs cannot communicate cor-
rectly with the other participants.
The smallest Wilo Net “communication network” consists of two participants (e.g. with
twin-head pumps or two single pumps as twin-head pump). Usually the participants are
then operated with ID 1 and ID 2. However, any other combination of IDs 1 ... 21 is pos-
sible as long as both IDs are different.
13.7
Setting the Bluetooth interface
Wilo-Smart Connect module BT
As soon as the Wilo-Smart Connect Module BT is plugged into the Wilo-Connectivity
interface, the “Settings – External interfaces – Bluetooth setting” menu appears on the
display.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......