Setting the control functions
208
WILO SE 2021-12
NOTICE
Only the analogue inputs AI3 and AI4 of the Stratos GIGA2.0 can process signal type
PT1000.
After these adjustments, Multi-Flow Adaptation is activated with the additional control
function “Multi-Flow Adaptation mixer”.
11.6
Adjustment - Manual operation
All control modes, which are selected via the setting assistant, can be overridden with
the functions of manual operation OFF, MIN, MAX, MANUAL.
DANGER
The pump can start despite the “OFF” function
The “OFF” function is not a safety function and is no replacement for disconnecting
the power supply for maintenance work. Functions such as pump kick can start up
the pump despite the “OFF” function being set.
• Always disconnect the pump from the power supply before carrying out any
work!
Manual operation functions can be selected in the menu
“Settings”
→
“Manual op-
eration”
“Manual operation (OFF, MIN, MAX, MANUAL)”
Function
Description
Control mode
Pump works according to the set controls.
OFF
Pump is switched off. Pump is not running.
All other set controls will be overridden.
MIN
The pump is set to minimum power.
All other set controls are overridden.
MAX
The pump is set to maximum power.
All other set controls are overridden.
MANUAL
Pump is working according to set control, which is meant
for the “MANUAL” function.
Table 29:
Functions of manual operation
The manual operation functions OFF, MAX, MIN, MANUAL correspond to the functions
Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL in their effect.
Ext. OFF, Ext. MAX, Ext. MIN and Ext. MANUAL can be triggered via the digital inputs or
via a bus system.
Priorities
Priority*
Function
1
OFF, External OFF (binary input), External OFF (bus system)
2
MAX, External MAX (binary input), External MAX (bus sys-
tem)
3
MIN, External MIN (binary input), External MIN (bus system)
4
MANUAL, External MANUAL (binary input)
Table 30:
Priorities
* Priority 1 = highest priority
NOTICE
The “MANUAL” function replaces all functions including those which are controlled
via a bus system.
If a monitored bus communication fails, the control mode set via the “MANUAL”
function is activated. (Bus Command Timer)
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......