Faults, causes and remedies
en
Installation and operating instructions Wilo-Stratos GIGA2.0-I, Wilo-Stratos GIGA2.0-D
257
Code
Fault
Cause
Remedy
615
Sensor source not suit-
ably configured.
Return temperature
sensor is not connec-
ted to correct source.
Input is not correctly
configured.
Configure source to “tem-
perature sensor” usage
type or select another
source.
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
618
Sensor source not avail-
able.
Return temperature is
not connected to ex-
isting CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
619
Sensor source not suit-
ably configured.
Temperature sensor
for “Heating/cooling
switchover” is not
connected to the
correct source. Input
is not correctly con-
figured.
Configure source to “tem-
perature sensor” usage
type or select another
source.
The sensor source is not correctly configured. In the context menu there is a
link for configuring the sensor source.
621
Sensor source not avail-
able.
Temperature value
for “Heating/cooling
switchover” is not
connected to existing
CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
641
Setpoint source not
suitably configured.
Setpoint is not con-
nected to correct
source. Input is not
correctly configured.
Configure source or
select another source.
The setpoint source for the cooling function is not correctly configured. In
the context menu there is a link for configuring the setpoint source.
642
Setpoint source not
available.
Setpoint not connec-
ted to existing CIF
module.
Insert CIF module.
Activate CIF module.
The setpoint source for the cooling function or the CIF module is not cor-
rectly configured. In the context menu there are links for configuration.
643
Sensor source not suit-
ably configured.
Sensor 1 is not con-
nected to correct
source. Input is not
correctly configured.
Configure source.
Select other source.
The sensor source for the cooling function is not correctly configured. In the
context menu there is a link for configuring the sensor source.
644
Same sensor source not
possible.
Sensor sources are
configured to the
same source.
Configure a sensor source
to another source.
The sensor sources for the cooling function are not correctly configured. In
the context menu there is a link for configuring the sensor sources.
646
Sensor source not avail-
able.
Sensor value is not
connected to existing
CIF module.
Insert CIF module.
Activate CIF module.
The sensor source or the CIF module is not correctly configured. In the con-
text menu there are links for configuration.
Содержание Stratos GIGA2.0-D
Страница 2: ...Fig I Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 D...
Страница 3: ...Fig II Stratos GIGA2 0 I Stratos GIGA2 0 D DN 40 DN 100 E E D...
Страница 4: ...Fig III Stratos GIGA2 0 I Stratos GIGA2 0 D DN 100 DN 125 D D E...
Страница 5: ...5 Deutsch 6 English 139 Fran ais 270 Nederlands 409...
Страница 548: ......
Страница 549: ......
Страница 550: ......
Страница 551: ......