![Vonsch FOTO CONTROL Series Скачать руководство пользователя страница 83](http://html1.mh-extra.com/html/vonsch/foto-control-series/foto-control-series_configuration-and-diagnostics_1049783083.webp)
RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 83 from 97
Name [ID]
Description
Def.
Signal
ID 27 [967]
-
Signal
ID 28 [968]
-
Signal
ID 29 [969]
-
Signal
ID 30 [970]
-
Signal
ID 31 [971]
-
Signal
ID 32 [972]
-
Signal
7.9.2 PROFIBUS
Group of parameters number [781]
Profibus is an open serial communication standard. Extension module Vonsch Profibus_UNI fully supports
the Profibus DP standard.
Detailed description of PROFIBUS communication protocol can be found on www.vonsch.sk, in the section
Support.
MENU \ SETTINGS \ COMMUNICATION \ PROFIBUS
Name [ID]
Description
Def.
PB Idle [782]
Selecting the way of reaction of the inverter to communication error, when either
inverter or master do not communicate with the Profibus module.
After the defined idle time, warning " W40-Reserved (page 30)" or fault " E37-
Profibus Timeout (page 33)" is generated.
□ Fault | □ Warning
PB
Fault
timeout [783]
Timeout of communication interruption with Master. After this time, fault E37-Profibus
Timeout (page 33) is generated.
5.0 s
0.1 s ÷ 3600.0
s
PB Warning
timeout [784]
MODBUS communication timeout, after which the warning " W42-Modbus Timeout
(page 30)" is generated. If a Modbus protocol fault and warning are evaluated at the
same time, see PB Idle [782] (page 83), then this parameter must be lower than the
parameter PB Fault timeout [783] (page 83), otherwise the warning does not apply.
2.0 s
0.1 s ÷ 3600.0
s
PB Warning
mode [785]
Defines what action should the inverter take after warning " W40-Reserved (page
30)" occurs.
Reset
Reset
Inverter goes to reset.
Stop
Inverter stops.
Quick stop
Inverter stops (Quick stop).
Nothing.
Inverter will not respond to warnings.
PB
Type
[1038]
Specifies the format of transmission of operational variables.
2
PD
values
2 PD values
It is possible to simultaneously transmit two variables only in the format described by the
documentation.
4 PD values It is possible to transmit 4 values as 16-bit numbers.
VQFREM
It is possible to transmit 4 values as 16-bit numbers, by addresses VQFREM.
PB
Options
[1177]
Format and data source settings.
□ Normalized
REF and ACT variables will be normalized to 4000h.
□ Fixed APD
Selection of PD variables, it is set by parameters [1176] (page 84), not by the