RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 55 from 97
Name [ID]
Description
Def.
R2 switch off
[368]
Conditions for R2 switch off.
Look choises of parameter's Inverter state [76] (page 25)
Relay 3
Group of parameters number [188]
Relay 3 setting. Relay is connected to the terminals: NC - X2:31, COM - X2:32, NO - X2:33.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 3
Name [ID]
Description
Def.
R3
Source
[639]
Relay switching function setting. Functionality is the same as RELAY 1 R1 Source
[637] (page 53).
Ready
Look choises of parameter's R1 Source [637] (page 53)
R3 switch on
time [377]
Relay switch-on time delay.
0.00 s
0.00
s
÷
3600.00 s
After establishment of the switch condition, the relay will switch-on after a selected amount
of time.
R3 switch-off
time [378]
Relay switch-off time delay.
0.00 s
0.00
s
÷
3600.00 s
If the switch condition is no longer valid, the relay remains switched on for a selected
amount of time.
R3 Logic [691]
Determines the relay output evaluation mode. The condition will be evaluated first,
then the switch times will be evaluated and the relay logic will be evaluated last.
Direct
Direct
If the switch conditions are met, the relay will switch on.
Inverted
If the switch conditions are met, the relay will switch off.
SPECIAL SETTING R3
Group of parameters number [263]
Special function setting for relay 3. R3 Source [639] (page 55) must be chosen as "Special".
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 3 \ SPECIAL SETTING R3
Name [ID]
Description
Def.
R3 Signal [373]
Signal that is evaluated for the relay switch. Either numeric or discrete
signal can be chosen.
[76]
Inverter
state
Signal
R3 switch on
[375]
Conditions for R3 switch on.
Ready
Look choises of parameter's Inverter state [76] (page 25)
R3 switch off
[391]
Conditions for R3 switch off.
Look choises of parameter's Inverter state [76] (page 25)
7.5.4 ANALOG OUTPUTS
Group of parameters number [145]
Analog outputs settings. Analog outputs are used to transfer continuous signals and quantities of the inverter
to superior control and diagnostic systems such as display units, PLC or measuring instruments.
AO1
Group of parameters number [416]
First analog output is connected to the terminal: Plus - X1:19, Minus - X1:20 (Plus - X1:15, Mínus - X1:16 for
UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO1
Name [ID]
Description
Def.
AO1 Type [415]
Analog output type.
0-20mA