RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 44 from 97
Name [ID]
Description
Def.
□ BIN2
□ BIN3
□ BIN4
□ BIN5
□ BIN6
□ Log. block 1
□ Log. block 2
□ Log. block 3
□ Log. block 4
□ Log. block 5
□ Log. block 6
□ Log. block 7
□ Log. block 8
□ Active
Always active. It can be used as logical 1.
Bit2 DS mask
[67]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
Bit3 DS mask
[71]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
Bit4 DS mask
[81]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
Bit5 DS mask
[85]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
Bit6 DS mask
[91]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
Bit7 DS mask
[94]
See Bit1 DS mask [58] (page 43).
Look choises of parameter's Bit1 DS mask [58] (page 43)
7.4 CONTROL AND REGULATION
Group of parameters number [11]
Parameter settings of inverter control.
MENU \ SETTINGS \ CONTROL AND REGULATION
Name [ID]
Description
Def.
Off-grid
mode [879]
Turning on or off the off-grid mode of the inverter.
turned off
turned off
Inverter requires stable three-phase grid to operate properly (ON-GRID).
turned on
Inverter serves as the standalone voltage source and controls the three-phase symmetric
voltage. It is not possible to connect the inverter to the grid in this mode.
Control
strategy
[878]
Switching the control strategy for two different control goals.
Vdc control
Vdc control
The inverter will control the DC link voltage and the transfered power will vary according to the
power on the DC side of the inverter.
active
power
control
The inverter will control the active power and the DC voltage will be controlled by another
device connected to it (booster, second inverter...). When this strategy is used, inverter cannot
be operated in off-grid mode.
Idc control
The inverter will control the DC current, while DC link voltage will be between Min. VDC [508]
(page 46) and Max. VDC [509] (page 46). When this strategy is used, inverter cannot be
operated in off-grid mode.