RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 56 from 97
Name [ID]
Description
Def.
Turned off
Analog output is turned off. The output is 0mA.
0-20mA
Analog output operates in the 0-20mA range.
4-20mA
Analog output operates in the 4-20mA range.
AO1 Signal [419]
Selection of special signal for the analog output.
[66] Active inv. power
Signal
Signal (AO1_A) [420]
Signal value for the analog output level in point A.
-20000.0 W
-9E6 W ÷ 9E6 W
Signal (AO1_B) [421]
Signal value for the analog output level in point B.
20000.0 W
-9E6 W ÷ 9E6 W
AO1_A [810]
Analog output level in point A.
0.00 mA
0.00 mA ÷ 20.00 mA
AO1_B [811]
Analog output level in point B.
20.00 mA
0.00 mA ÷ 20.00 mA
AO2
Group of parameters number [417]
Second analog output is connected to the terminal: Plus - X1:21, Minus - X1:22 (Plus - X1:17, Minus - X1:16
for UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO2
Name [ID]
Description
Def.
AO2 Type [422]
Analog output type. Configuration possibilities are the same as in AO 1
AO1 Type [415] (page 55).
0-20mA
Look choises of parameter's AO1 Type [415] (page 55)
AO2 Signal [423]
Selection of the signal that will linearly recalculate the analog output.
[313]
Grid
current
Signal
Signal (AO2_A)
[424]
Signal value for the analog output level in point A.
0.00 A
0.00 ÷ I
max
8
8
Refer to chapter 3.3
(str. 14) by product type.
Signal (AO2_B)
[425]
Signal value for the analog output level in point B.
30.00 A
0.00 ÷ I
max
8
8
Refer to chapter 3.3
(str. 14) by product type.
AO2_A [812]
Analog output level in point A.
0.00 mA
0.00 mA ÷ 20.00
mA
AO2_B [813]
Analog output level in point B.
20.00 mA
0.00 mA ÷ 20.00
mA
AO3
Group of parameters number [418]
Third analog output is connected to the terminal: Plus - X1:23, Minus - X1:24. Not available for the UNIFREM
400 M converters.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG OUTPUTS \ AO3
Name [ID]
Description
Def.
AO3 Type [426]
Analog output type. Configuration possibilities are the same as in AO 1
AO1 Type [415] (page 55).
Turned off
Look choises of parameter's AO1 Type [415] (page 55)
AO3 Signal [427]
Selection of the signal that will linearly recalculate the analog output.
[66] Active inv.
power
Signal
Signal (AO3_A)
Signal value for the analog output level in point A.
100.0 W