SPECIAL SETTING AIN4
Group of parameters number [68]
Analog input mapping setting for the selected parameter. Value of this parameter will be affected by the
analog input value.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG INPUTS \ AIN4 \ SPECIAL SETTING AIN4
Name [ID]
Description
Def.
AIN4 Signal [349]
Selection of the signal that will be linearly recalculated according to the analog
input.
-
Signal
Signal
(AIN4_A)
[350]
Signal value for the analog input level in point A.
-
- ÷ -
Signal
(AIN4_B)
[351]
Signal value for the analog input level in point B.
-
- ÷ -
AIN4_A [588]
Analog input level in point A.
0.00 V
0.00 V ÷ 10.00 V
AIN4_B [578]
Analog input level in point B.
20.00
V
0.00 V ÷ 10.00 V
7.5.3 RELAY OUTPUTS
Group of parameters number [146]
Relay outputs setting, which can be used for signalization of discrete values and events of the inverter, e.g.
fault, run.
Relay 1
Group of parameters number [186]
Relay 1 setting. Relay is connected to the terminals: NC - X2:25, COM - X2:26, NO - X2:27 (NC - X2:24,
COM - X2:25, NO - X2:26 for UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 1
Name [ID]
Description
Def.
R1
Source
[637]
Relay switching function setting.
Run
Run
Relay will switch on when the inverter is in start (running).
Ready
Relay will switch on when the inverter is READY.
Fault
Relay wil switch on when the fault in the inverter occurs.
Special
R1 switch on
time [362]
Relay switch-on time delay.
0.00
s
0.00
s
÷
3600.00 s
After establishment of the switch condition, the relay will switch-on after a selected amount
of time.
R1 switch-off
time [363]
The relay switch-off time delay.
0.00
s
0.00
s
÷
3600.00 s
After termination of the switch condition, the relay will switch-off after a selected amount of
time.
R1 Logic [689]
Determines the relay output evaluation mode. The condition will be evaluated first,
then the switch times will be evaluated and the relay logic will be evaluated last.
Direct