Name [ID]
Description
Def.
Low
ETP
temperature
[1002]
When ETP temperature drops below this value, inverter generates a fault E38-ETP
temperature (page 33) because of the extremely low temperatures, which can be
caused by incorrect wiring or damage of ETP sensor. When ETP Type set to "PTC
thermistor", this parameter has no meaning.
-100.0
°C
-500.0
°C
÷
500.0 °C
ETP
maximal
current [938]
Maximal ETP measuring current.
10.00
mA
0.01 mA ÷ 20.00
mA
CUSTOM SENSOR
Group of parameters number [779]
Setting the characteristic of the custom ETP sensor (if "Custom sensor" is selected in ETP Type [792] (page
71)).
MENU \ SETTINGS \ FUNCTIONS \ EXTERNAL THERMAL PROTECTION (ETP) \ CUSTOM SENSOR
Name [ID]
Description
Def.
Resistance by 20°C
[794]
Resistance value of an external temperature sensor in 20°C, in case that the
sensor characteristics is user-defined.
1200.0
Ω
0.1 Ω ÷ 99000.0 Ω
Resistance in 100°C
[795]
Resistance value of an external temperature sensor in 100°C, in case that the
sensor characteristics is user-defined.
4600.0
Ω
0.1 Ω ÷ 99000.0 Ω
SPECIAL SETTING ETP
Group of parameters number [571]
Special source setting for the ETP voltage drop measurement.
MENU \ SETTINGS \ FUNCTIONS \ EXTERNAL THERMAL PROTECTION (ETP) \ SPECIAL SETTING ETP
Name [ID]
Description
Def.
U ETP Signal [95]
Selecting the signal, which should be evaluated as voltage on the ETP sensor.
-
Signal
Usually an analog input in the 0 to 10 V mode is used.
7.6.5 S0 measure
Group of parameters number [1039]
Setting the S0 measurement channel for energy meter.
MENU \ SETTINGS \ FUNCTIONS \ S0 MEASURE
Name [ID]
Description
Def.
S0 pulses [1040]
Number of pulses from energy meter corresponding to 1kW (1kVAr).
1000
1 ÷ 20000
S0 source [1041]
Selection of max. 4 binary inputs representing the S0 measurement channels.
Look choises of parameter's Binary inputs [184] (page 21)
7.7 FAULTS AND WARNINGS
Group of parameters number [136]
Setting the parameters affecting the conditions of generation and termination of inverter fault states.
MENU \ SETTINGS \ FAULTS AND WARNINGS
Name [ID]
Description
Def.
Clear history [494]
This command clears the inverter fault history. There will be no record in the history.
7.7.1 OPTIONAL FAULTS