Name [ID]
Description
Def.
term D [314]
0.000 s ÷ 1.000
s
D term filter
[13]
Filter time constant of the derivation term of the process controller.
0.0 ms
0.0 ms ÷ 1000.0
ms
Filter is turned off when set to 0 s.
Parking [335]
Parking is a function, which automatically deactivates the START, if the parking
conditions Depark. hyst. [341] (page 68) and Parking time [347] (page 68) are met.
If the PC operates at its low limit for the time Parking time [347] (page 68),
converter blocks the START. This can occur if the controlled quantity exceeds the
setpoint value and the PC output is at minimum. If the regulation error changes so it
exceeds the value Depark. hyst. [341] (page 68), the START block will be undone
and PC starts to regulate. This function is used to prevent unnecessary operation of
the device and saving the energy when the regulation has no major impact on the
controlled quantity.
Turned
off
Turned off
Parking is turned off.
Turned on
Parking is turned on.
Depark. hyst.
[341]
The value the regulation error, when parking of the inverter is canceled (parking =
disabling the Start block).
-
- ÷ -
Parking
time
[347]
Time that has to pass, when the parking conditions are met, to park the PC (parking
= blocking the Start).
60.0 s
0.1 s ÷ 3200.0 s
PC Initialization
Group of parameters number [978]
Setting the initialization (reset) signal of the PC output and the I-term to the defined value.
MENU \ SETTINGS \ FUNCTIONS \ PROCESS CONTROLLER \ PC INITIALIZATION
Name [ID]
Description
Def.
PC
Reset
signal [385]
Process controller reset signal.
-
Signal
After activating the process controller reset signal, the integration term and the PC output
are set to value given by the parameter PC Reset value [977] (page 68).
PC Reset [762]
Conditions for PC reset.
-
- ÷ -
PC
Reset
inactive [976]
Deactivation of PC reset: In case of a numeric signal if the signal value is lower
than the defined level.
-
- ÷ -
PC Reset value
[977]
Value that is set by the inverter to the output and the PC integration term after an
active PC reset.
0.0000
-1.0000
÷
1.0000
SPECIAL SETTING PC
Group of parameters number [570]
Special setting of the process controller signals.
MENU \ SETTINGS \ FUNCTIONS \ PROCESS CONTROLLER \ SPECIAL SETTING PC
Name [ID]
Description
Def.
Setpoint
signal [40]
Selection of the parameter that represents the setpoint value of the process controller.
The value is applied if the parameter Source of PC setpoint [86] (page 67) is set to
"Special".
-
Signal
Selected parameter is automatically recalculated to the range of regulation of the process