RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 18 from 97
Name [ID]
Description
Dim.
Production kWh [259]
Produced energy (kWh) counter. This counter can be preset or reset by
[414] (page 38).
kWh
Production MWh [260]
Produced energy (MWh) counter. This counter can be preset or reset by
MWh
kWh Consumption [257]
Consumed energy (kWh) counter. This counter can be preset or reset by
[414] (page 38).
kWh
MWh
Consumption
[258]
Consumed energy (MWh) counter. This counter can be preset or reset by
[414] (page 38).
MWh
Production today [1067]
Only produced energy for present day.
kWh
Consumption
today
[1068]
Only consuption energy for present day.
kWh
4.3 Command
Group of parameters number [737]
Quantities affecting the inverter control, inputs and outputs.
MENU \ DIAGNOSTICS \ COMMAND
Name [ID]
Description
Dim.
Panel setpoint [161]
Setpoint value from the panel, entered in the monitor window.
DC voltage reference
[220]
DC voltage reference, its source is set by parameter DC voltage reference [293]
(page 41).
AC voltage ref. [875]
Value of AC voltage reference, which source is selected by AC voltage ref. [873]
(page 41).
V
Phi angle ref. [356]
Phase difference reference between voltage and current. Positive value
represents the capacitive nature and negative value the inductive nature of
generated current.
°
Grid power ref. [883]
Active grid-side power reference, when the "active power control" is set by
Control strategy [878] (page 44).
W
Reactive power ref.
[975]
Reactive power reference. Reactive power control is possible only for PF
CORRECTOR device type.
VAr
Discrete
setpoint
[574]
Discrete setpoint value [559] (page 42).
Control word [77]
Control signals of the inverter.
□ START
Control command for the motor operation mode (1 - starts the inverter).
□ Bit 1
Reserved
□ RESET PWM
Control command for the immediate voltage cut-off on the inverter output (active -
turns off PWM).
□ FAULT ACK.
Command for fault acknowledgement.
□ ERR_MASTER
Master fault
□ COMPENSATION
DT
Turn on the dead time compensation mode
□ Bit 6
Reserved
□ UNF BOARD TYPE 0 - UNF 400, 1 - UNF 230/400 M.
ON / OFF time [686]
Represents the time in AUTO OFF mode to the next automatic start or stop of
the inverter.
Random time [807]
Value of random time according to the parameter Random time [806] (page 40). s
4.4 Control
Group of parameters number [738]
Quantities affecting the inverter control, values of important control and operating quantities.
MENU \ DIAGNOSTICS \ CONTROL
Name [ID]
Description
Dim.
V ramp ref.
Output of the AC or DC voltage reference ramp according to the chosen mode of V