RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 46 from 97
Name [ID]
Description
Def.
proportional term.
-1000.0000
÷
1000.0000
PR controller works only when using the PR source active selection from the power
restriction signal. If the proportional gain is negative, then regulation error is inverted.
I gain PR [1049]
Integration time constant value of the power restriction
(PR) controllers proportional term.
1.00 s
0.00 s ÷ 1000.00
s
PR controller works only when using the PR source active selection from the power
restriction signal.
Power
rise
[%/min] [1061]
Power rise rate when the power restriction value is
decreasing (power is rising).
600000 %
1 % ÷ 600000 %
7.4.2 VOLTAGE RAMPS
Group of parameters number [114]
Setting of ramps for AC,DC voltage references and their limits.
MENU \ SETTINGS \ CONTROL AND REGULATION \ VOLTAGE RAMPS
Name [ID]
Description
Def.
Max. VDC [509]
Upper limit of the DC voltage reference.
680.0 V
Min. VDC [508] ÷
Overvoltage
2
For PV power plant inverters control (FOTO CONTROL), it represents the upper limit
of MPPT range.
2
Refer to chapter 3.1
(str. 13) by product type.
Min. VDC [508]
Lower limit of the DC voltage reference.
450.0 V
Undervoltage
1
÷
Overvoltage
2
For PV power plant inverters control (FOTO CONTROL), it represents the lower limit
of MPPT range.
1
Refer to chapter 3.1
(str. 13) by product type.
2
Refer to chapter 3.1
(str. 13) by product type.
Max. V AC [876]
The upper limit of the RMS value of phase-to-phase AC voltage reference. 420.0 V
Min. V AC [877] ÷ AC
Overvoltage [627]
In the off-grid mode Off-grid mode [879] (page 44), this value represents the upper
limit of the of output voltage range.
Min. V AC [877]
The lower limit of the RMS value of phase-to-phase AC voltage reference. 100.0 V
0.0 ÷ AC Overvoltage
[627]
In the off-grid mode Off-grid mode [879] (page 44), this value represents the lower
limit of the of output voltage range.
Ramp-up time V [116]
Time, during which the voltage reference rises from minimum to maximum
value.
2.0 s
0.1 s ÷ 3000.0 s
Too short ramp times of reference voltage can result in significant swells of grid-side
current and inverter current after changing the voltage reference or by the MPPT
algorithm for FOTO CONTROL inverters.
Ramp-down time V
[119]
Time, during which the voltage reference falls from maximum to minimum
value.
2.0 s
0.1 s ÷ 3000.0 s
Too short ramp times of reference voltage can result in significant swells of grid-side
current and inverter current after changing the voltage reference or by the MPPT
algorithm for FOTO CONTROL inverters.
Init. V ramp [1035]
Selection of method of voltage ramp initialization when not operating.
to Vdc
to Vdc
Voltage ramp is set to the actual value of Vdc.
to Vdc_max
Voltage ramp is set to the value of Max. VDC [509] (page 46).
Ramp VDC min/max
[1200]
Rate of change of Max. VDC [509] (page 46) and Min. VDC [508] (page
46) in V/s.
100.0 V
0.1 V ÷ 10000.0 V
7.4.3 CONTROLLERS
Group of parameters number [295]
Parameters of main controller loops of the inverter. It is not recommended to change any parameters without
consultation with VONSCH s.r.o. employees.
MENU \ SETTINGS \ CONTROL AND REGULATION \ CONTROLLERS
Name [ID]
Description
Def.
Filter Vd [760]
Filter constant of feedforward signal from the grid voltage for the 0.2000 s