Name [ID]
Description
Def.
Pressure atm
Controlled quantity is the pressure in atmosphere [atm].
Pressure
at
inverted
Controlled quantity is the pressure in atmosphere [atm], error is inverted.
Temperature
Controlled quantity is the temperature in degree Celsius [°C].
Temperature
inverted
Controlled quantity is the temperature in degree Celsius [°C], error is inverted.
Position
Controlled quantity is the position.
Position
inverted
Controlled quantity is the position, error is inverted.
Flow
Controlled quantity is the flow.
Flow inverted
Controlled quantity is the flow, error is inverted.
Relative
Controlled quantity is in relative units.
Relative
inverted
Controlled quantity is in relative units, error is inverted.
Voltage
Controlled quantity is the voltage.
Voltage
inverted
Controlled quantity is the voltage, error is inverted.
Current
Controlled quantity is the current.
Current inverted Controlled quantity is the current, error is inverted.
Power
Controlled quantity is the power.
Power inverted Controlled quantity is the power, error is inverted.
Source of PC
setpoint [86]
Selecting the setpoint value of the process controller.
Value
Value
Parameter Source of PC setpoint [86] (page 67) will be used as the source.
AIN1
Analog input AIN1 will be used as the PC Setpoint value source.
AIN2
Analog input AIN2 will be used as the PC Setpoint value source.
AIN3
Analog input AIN3 will be used as the PC Setpoint value source.
AIN4
Analog input AIN4 will be used as the PC Setpoint value source.
Special
The special setting Setpoint signal [40] (page 68) will be used as the source.
Setpoint value
[39]
Process controller setpoint value. Value applies if the parameter Source of PC
setpoint [86] (page 67) is set to "Value".
- ÷ -
PC
feedback
source [92]
Process controller feedback source setting. Feedback represents the actual value of
controlled quantity. It is usually a signal from the sensor or measurement inverter.
Value
Look choises of parameter's Source of PC setpoint [86] (page 67)
Feedback [61]
Process controller feedback value. Value applies if no signal is chosen PC feedback
source [92] (page 67)..
-
- ÷ -
Min. setpoint
value [63]
Minimal value of the possible setpoint value range.
-
- ÷ -
Max. setpoint
value [64]
Maximal value of the possible setpoint value range.
-
- ÷ -
Dead-zone [65]
Process controller dead-zone(insensitivity) for small changes of the error value.
-
- ÷ -
Setting a non-zero dead-zone can suppress the oscillations at the PC output caused by
noise at the control error Error PC [438] (page 24), but can also cause steady-state error,
which is proportional to the value of dead-zone.
Proportional
term P [80]
Proportional gain of the process controller.
1.00
0.00 ÷ 30.00
Integration
term I [208]
Time constant of the integration term of the process controller.
10.00 s
0.01 s ÷ 600.01
s
Derivation
Time constant of the derivation term of process controller.
0.000 s