RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 48 from 97
Name [ID]
Description
Def.
Hz
Freq. 0% power
[1063]
Frequency threshold for 0% power for DROOP CONTROL feature. Inverter is
disconnected when frequency is above this threshold.
52.50
Hz
1.00 Hz ÷ 1000.00
Hz
Filter of freq.
[1064]
Filter constant of the frequency.
0.20 s
0.00 s ÷ 60.00 s
7.4.5 DC CURR. CONTROLLER
Group of parameters number [1153]
Parameters for DC current controller.
MENU \ SETTINGS \ CONTROL AND REGULATION \ DC CURR. CONTROLLER
Name [ID]
Description
Def.
IDC setpoint [1154]
DC current setpoint value.
0.00 A
-3000.00 A ÷ 3000.00 A
P term IDC cont. [1155]
P term of DC current PI controller.
1.50
0.00 ÷ 25.00
I term IDC cont. [1156]
I term of DC current PI controller.
0.200 s
0.001 s ÷ 1000.000 s
Curr. ramp charge [1157]
Current ramp for DC link / battery charging.
50.00 A
0.01 A ÷ 1E06 A
Curr. ramp discharge [1158]
Current ramp for DC link / battery discharging.
50.00 A
0.01 A ÷ 1E06 A
7.5 INPUTS AND OUTPUTS
Group of parameters number [486]
Setting of the control, digital and analog inputs and outputs of inverter.
7.5.1 BINARY INPUTS
Group of parameters number [143]
Binary (digital) inputs setting.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ BINARY INPUTS
Name [ID]
Description
Def.
BIN
HW
Type [172]
Binary inputs hardware evaluation setting. The evaluation covers all digital inputs
simultaneously.
24V Level
0V Level
Individual binary inputs X1:1, X1:2, X1:3, X1:4, X1:5, X1:6 are active when 0V voltage is
connected (Terminal X1:10).
24V Level
Individual binary inputs X1:1, X1:2, X1:3, X1:4, X1:5, X1:6 are active when 24V voltage is
connected (Terminal X1:8).
BIN1 Filter
[178]
Time constant of the binary signal filter.
10 ms
0
ms
÷
30000 ms
Binary input is switched on when the voltage level defined by parameter BIN HW Type [172]
(page 48) is present longer than the value of this parameter and is switched off when the voltage
is not present longer than the value of this parameter.
BIN1 Logic
[657]
Determines the binary input evaluation mode. Binary input hardware settings need
to be taken into account.
Direct
Direct
If the HW Type is set to 24V, then the BIN is active if there is 24V on the input. If the HW Type is
set to 0V, then the BIN is active on 0V.
Inverted
If the HW Type is set to 24V, then the BIN is active by 0V. If the HW Type is set to 0V, then the
BIN is active by 24V.
BIN2 Filter
[179]
Time constant of the binary signal filter.
10 ms