Group of parameters number [190]
Turning on/off the evaluation of some fault states.
MENU \ SETTINGS \ FAULTS AND WARNINGS \ OPTIONAL FAULTS
Name [ID]
Description
Def.
AIN Fault [790]
This parameter turns on / off testing of the analog input faults. The fault is
evaluated only if the input is set to 4-20mA or 2-10V, output value is under the
minimal value and the fault testing is turned on.
Is
evaluated
Is evaluated
If the analog input is for a long time under the minimal value, the inverter generates the
fault.
Is not evaluated Inverter accepts any analog input value.
External fault
source [264]
Setting the source of the external fault. If the source is active, the fault " E7-
External fault (page 32)" is generated. Is used as an emergency stop. Fault
blocks the inverter operation.
Special
Look choises of parameter's Reset source [645] (page 39)
SPECIAL SETTING
Group of parameters number [265]
Setting the special source of the external fault.
MENU \ SETTINGS \ FAULTS AND WARNINGS \ OPTIONAL FAULTS \ SPECIAL SETTING
Name [ID]
Description
Def.
Ext. fault signal
[487]
Signal that is evaluated if the fault " E7-External fault (page 32)" occurs
or not. Either a numeric or a bit signal can be chosen.
[184]
Binary
inputs
Signal
External
fault
[488]
Conditions for external fault.
BIN2 | BIN4 |
BIN5 | BIN6
Look choises of parameter's Binary inputs [184] (page 21)
External
fault
inactive [489]
External fault deactivation: In case of a numeric signal if the signal value
is lower than the defined level.
Look choises of parameter's Binary inputs [184] (page 21)
7.7.2 GRID TEST
Group of parameters number [772]
Grid voltage test parameters for evaluation grid faults (overvoltage, undervoltage, frequency).
MENU \ SETTINGS \ FAULTS AND WARNINGS \ GRID TEST
Name [ID]
Description
Def.
Fast AC overvoltage
[667]
Threshold for fast AC overvoltage. Represents the RMS value of the
voltage.
450.0 V
V
grid
3
÷ V
acmax
4
If AC voltage [221] (page 19) exceeds this value for longer than the time set by Fast
time V AC [770] (page 73), fault E15-Extr. overvoltage (page 32) is generated.
3
Refer to chapter 3.1
(str. 13) by product type.
4
Refer to chapter 3.1
(str. 13) by product type.
Fast
AC
undervoltage [668]
Threshold for fast AC undervoltage. Represents the RMS value of the
voltage.
330.0 V
0.0 ÷ V
grid
3
If AC voltage [221] (page 19) falls below this value for longer than the time set by
Fast time V AC [770] (page 73), fault E13-Extr. undervoltage (page 32) is generated.
3
Refer to chapter 3.1
(str. 13) by product type.
Fast time V AC [770]
Response time for generating the fast grid failures E13-Extr. undervoltage
(page 32) and E15-Extr. overvoltage (page 32).
0.010 s
0.001 s ÷ 10.000 s
Adjusts sensitivity to fault evaluation. Setting response time of grid failure must
correspond to the terms for connection to the distribution grid.
AC
Overvoltage
[627]
Maximum permissible value of grid voltage.
440.0 V
V
grid
3
÷ Fast AC
RMS value of maximum permissible phase-to-phase voltage on terminals L1, L2, L3.
After rise of AC voltage [221] (page 19) above this value for the time given by Time V
AC [771] (page 74), inverter generates a fault E35-Grid overvoltage (page 33).