Name [ID]
Description
Def.
Direct
If the switch conditions are met, the relay will switch on.
Inverted
If the switch conditions are met, the relay will switch off.
SPECIAL SETTING R1
Group of parameters number [215]
Special function setting for relay 1. R1 Source [637] (page 53) must be chosen as "Special".
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 1 \ SPECIAL SETTING R1
Name [ID]
Description
Def.
R1 Signal [357]
Signal that is evaluated for the relay switch. Either numeric or discrete
signal can be chosen.
[76]
Inverter
state
Signal
R1 switch on
[359]
Conditions for R1 switch on.
Operation
Look choises of parameter's Inverter state [76] (page 25)
R1 switch off
[360]
Conditions for R1 switch off.
Look choises of parameter's Inverter state [76] (page 25)
Relay 2
Group of parameters number [187]
Relay 2 setting. Relay is connected to the terminals: NC - X2:28, COM - X2:29, NO - X2:30 (NC - X2:21,
COM - X2:22, NO - X2:23 for UNIFREM 400 M).
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 2
Name [ID]
Description
Def.
R2
Source
[638]
Relay switching function setting. Functionality is the same as RELAY 1 R1 Source
[637] (page 53).
Special
Look choises of parameter's R1 Source [637] (page 53)
R2 switch on
time [370]
Relay switch-on time delay.
0.00 s
0.00
s
÷
3600.00 s
After establishment of the switch condition, the relay will switch-on after a selected amount
of time.
R2 switch-off
time [371]
Relay switch-off time delay.
0.00 s
0.00
s
÷
3600.00 s
If the switch condition is no longer valid, the relay remains switched on for a selected
amount of time.
R2 Logic [690]
Determines the relay output evaluation mode. The condition will be evaluated first,
then the switch times will be evaluated and the relay logic will be evaluated last.
Direct
Direct
If the switch conditions are met, the relay will switch on.
Inverted
If the switch conditions are met, the relay will switch off.
SPECIAL SETTING R2
Group of parameters number [216]
Special function setting for relay 2. R2 Source [638] (page 54) must be chosen as "Special".
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ RELAY OUTPUTS \ RELAY 2 \ SPECIAL SETTING R2
Name [ID]
Description
Def.
R2 Signal [365]
Signal that is evaluated for the relay switch. Either numeric or discrete
signal can be chosen.
[76]
Inverter
state
Signal
R2 switch on
[367]
Conditions for R2 switch on.
Fault
Look choises of parameter's Inverter state [76] (page 25)