Name [ID]
Description
Dim.
Last Addr. [609]
Last received address of the device.
hex
Last Func. [610]
Last received function (may also be another device).
hex
Last register [673]
Last received register (only for this device, it is shown first if there is access to
multiple registers).
hex
Last result [611]
Result of the last received function determined for this device.
hex
Last length [612]
Size (in bytes) of the last received frame over MODBUS.
Last CRC [613]
Last received CRC (it can also be a frame for another device)
hex
Message count [674]
Count of all received messages, including error messages.
hex
CRC
error
count
[615]
Count of all received CRC error count messages.
hex
Exception
count
[763]
Number of messages, which are responded by the error messages.
hex
Slave count [764]
Count of received messages with a valid device address.
hex
No response [765]
Count of received messages with a valid device address, when the device did
not respond.
hex
4.9.2 PROFIBUS
Group of parameters number [786]
PROFIBUS diagnostics.
MENU \ DIAGNOSTICS \ COMMUNICATION \ PROFIBUS
Name [ID]
Description
Dim.
Profibus
setpoint
value [778]
Setpoint value received over the Profibus protocol.
%
SW_PB [775]
Status word sent over the Profibus communication. For a more detailed
description, see the documentation for Profibus Extension Module.
□ Ready To Switch
On
Convert Reset, Quick stop are inactive, no faults or initialization are present.
□ Ready To Operate Inverter is ready for the start command.
□ Operation Enabled Inverter generates voltage on the outputs.
□ Fault Present
Inverter is in fault.
□ No OFF 2
Inactive - Reset is active, outputs of the inverter are blocked, active - Reset is not
active.
□ No OFF 3
Inactive - Quick stop is active, active - Quick stop is inactive.
□
Switching
On
Inhibited
Reset or Quick stop are active, or an initialization or fault are present.
□ Warning Present
Warning or functional message occurred in the inverter.
□ Speed Error within
tolerance
When active, the setpoint frequency is achieved.
□ Control Requested
Inactive - inverter does not accept Control Word over communication. Acitve - inverter
is controlled by Control Word received over communication.
□ F or n Reached
When active, the setpoint frequency is achieved.
□ Run
Inverter generates voltage on the outputs.
□ Set b0
Bit 0 of active set binary combination.
□ Set b1
Bit 1 of active set binary combination.
□ LB3
Status of logical block 3.
□ LB4
Status of logical block 4.
CW_PB [776]
Command word sent by the Profibus master. For a more detailed description,
see the documentation for Profibus Extension Module.
□ ON
Inverter is ready to accept the START command.
□ No OFF 2
Inactive - Reset is active, Active - normal inverter operation.
□ No OFF 3
Inactive - Quick stop is active, active - normal inverter operation.
□ Enable Operation Start. Inverter starts generating voltage on its output terminals.
□
Enable
Ramp
Generator
Inactive - ramp input is set to zero, active - normal operation of the ramp input block.
□ Unfreeze Ramp
Inactive - ramp output is frozen, active - ramp is operating normally.