RU , GSE, FOTO CONTROL, QUATROFREM v.2.53x
15. apríla 2019
Page 38 from 97
Name [ID]
Description
Def.
conditions for termination of trial operation.
**** ÷ ****
Calculation of
harmonics
[846]
The choice of method of calculating current and voltage harmonics in
diagnostic parameter groups [223] (page 19) and [240] (page 20).
absolute
relative
The current and voltage harmonics are related to the RMS actual value of the first
harmonic of current and voltage.
absolute
The current and voltage harmonics are related to the RMS nominal value of current and
voltage. This method of evaluation is appropriate when using the value of harmonics for
control quality tests.
7.2.1 ENERGY CONS. SETTING
Group of parameters number [414]
Preset or reset of consumed and produced energy counters [567] (page 17).
MENU \ SETTINGS \ INVERTER PARAMETERS \ ENERGY CONS. SETTING
Name [ID]
Description
Def.
Cons. kWh preset [410]
Preset of consumed energy (kWh).
0 kWh
0 kWh ÷ 1E7 kWh
Cons. MWh preset [411]
Preset of consumed energy (MWh).
0 MWh
0 MWh ÷ 1E7 MWh
Prod. kWh preset [412]
Preset of produced energy (kWh).
0 kWh
0 kWh ÷ 1E7 kWh
Prod. MWh preset [413]
Preset of produced energy (MWh).
0 MWh
0 MWh ÷ 1E7 MWh
Reset prod. stats [679]
This command resets the stats of produced and consumed energy.
Source of stats reset [937]
Special source of production stats reset.
Look choises of parameter's Bit1 DS mask [58] (page 43)
7.3 COMMANDS
Group of parameters number [1]
Command settings of the inverter.
7.3.1 START RESET
Group of parameters number [193]
Settings of inverter START, RESET commands.
After START command, inverter turns on DC link voltage and current control, while maintaining the reactive
component of power to the reference value.
MENU \ SETTINGS \ COMMANDS \ START RESET
Name [ID]
Description
Def.
Start source
[194]
Setting of START command source. After the START command inverter generates
the voltage on L1,L2 and L3 terminals.
Control
panel
Control
panel
Pressing the green START button on the control panel causes the inverter to start. The start is
canceled by pressing the red STOP button.
Permanent
start
The inverter starts immediately after the switch on.
BIN1
The inverter start after the activation of the 1st binary input.
BIN2
The inverter starts after the activation of the 2nd binary input.
BIN3
The inverter starts after the activation of the 3rd binary input.
BIN1, 2
The inverter starts after the activation of the 1st or 2nd binary input.
BIN1, 3
The inverter starts after the activation of the 1st or 3rd binary input.
BIN1, 4
The inverter starts after the activation of the 1st or 4th binary input.
MODBUS
The inverter start is controlled over the serial communication. See the MODBUS serial
communication protocol.