7.7.3 HARMONICS CHECK
Group of parameters number [191]
Parameters for enabling and configuring the check of harmonic currents and voltages. The long-term
increase in harmonic distortion can be caused by rapid deterioration of connected distribution network, by
damage of the inverter or incorrect parameter adjustment.
MENU \ SETTINGS \ FAULTS AND WARNINGS \ HARMONICS CHECK
Name [ID]
Description
Def.
I
harm.
check
[505]
Turning on the check of high harmonic
currents [223] (page 19) and selection of
individual harmonics. The test is performed
only when the inverter is running.
2nd harm. I | 3rd harm. I | 4th harm. I | 5th harm. I |
6th harm. I | 7th harm. I | 8th (9th) harm. I | 9th
(11th) harm. I | 11th (15th) harm. I | 13th (19th)
harm. I | 15th (21st) harm. I | 17th (22nd) harm. I |
19th (23rd) harm. I | 21st (24th) harm. I
□ turn on
test harm.
When this choice is active, the sum of harmonic currents is calculated. When this sum exceeds
the value of Max. harm. I [825] (page 75) for more than Filter harm. fault [845] (page 76), the
fault E43-I harmonics (page 33) is generated.
■
2nd
harm. I
selection of individual harmonic.
■
3rd
harm. I
selection of individual harmonic.
■
4th
harm. I
selection of individual harmonic.
■
5th
harm. I
selection of individual harmonic.
■
6th
harm. I
selection of individual harmonic.
■
7th
harm. I
selection of individual harmonic.
■ 8th (9th)
harm. I
selection of individual harmonic.
■
9th
(11th)
harm. I
selection of individual harmonic.
■
11th
(15th)
harm. I
selection of individual harmonic.
■
13th
(19th)
harm. I
selection of individual harmonic.
■
15th
(21st)
harm. I
selection of individual harmonic.
■
17th
(22nd)
harm. I
selection of individual harmonic.
■
19th
(23rd)
harm. I
selection of individual harmonic.
■
21st
(24th)
harm. I
selection of individual harmonic.
Max.
harm.
I
[825]
Threshold of sum of selected current
harmonics.
15.00 %
0.00 % ÷
1000.00 %
V
harm.
check
[843]
Turning on the check of high harmonic
voltages [240] (page 20) and selection of
individual harmonics. The test is performed
2nd harm. V | 3rd harm. V | 4th harm. V | 5th harm.
V | 6th harm. V | 7th harm. V | 8th (9th) harm. V |
9th (11th) harm. V | 11th (15th) harm. V | 13th