Name [ID]
Description
Dim.
hours [499]
This value can be reset by authorized technicians only.
Operational hours
[500]
Operational hours. Inverter operation time. This value can be reset by the service
access only.
h
Warning [283]
State of individual warnings.
Warning2 [22]
State of individual warnings.
Fault [687]
State of individual faults.
Fault2 [688]
State of individual faults.
4.8 Thermal protections
Group of parameters number [512]
Diagnostic group of quantities regarding the thermal protections and overloads.
MENU \ DIAGNOSTICS \ THERMAL PROTECTIONS
Name [ID]
Description
Dim.
Cooler
temperature
[74]
Temperature of the power elements cooler. Inverter generates a warning " W6-Cooler
temperature (page 29)" after exceeding the temperature set by Cooler temperature
warning [699] (page 78). Inverter generates the fault " E1-Cooler temperature (page
32)" after exceeding the critical temperature. If the temperature falls below minimal limit
of sensor, this value is inaccessible.
If the cooler temperature drops under the minimal measuring range, the displayed
value is inaccessible.
°C
CB
temperature
[75]
Control board (CB) temperature. When the temperature exceeds the parameter CB
temperature warning [870] (page 78) inverter generates the warning " W7-CB
temperature (page 29)". After exceeding the critical temperature inverter generates the
fault " E22-CB temperature (page 32)". If the temperature falls below minimal limit of
sensor, this value is inaccessible.
If the temperature drops under the minimal limit of the measurement channel, the
displayed value is inaccessible.
°C
Thermal
integral
INV
[440]
Warming rate of the inverter. The fault " E8-Inverter overload (page 32)" occurs after
exceeding 100% of this value.
%
Thermal
integral
INV
[217]
Time remaining until the end of fault " E8-Inverter overload (page 32)".
s
Fan
duty
[1199]
Maximum PWM duty cycle of the inbuilt fan.
%
4.9 Communication
Group of parameters number [262]
Information regarding serial communications MODBUS, PROFIBUS, RS485, CAN.
4.9.1 MODBUS
Group of parameters number [608]
MODBUS protocol diagnostics on the RS 485 and USB ports.
MENU \ DIAGNOSTICS \ COMMUNICATION \ MODBUS
Name [ID]
Description
Dim.
Modbus
setpoint
value [830]
Setpoint value from the Modbus protocol.
%
SW_MODBUS [831]
State word sent over the Modbus communication. For a more detailed
description, see the documentation for MODBUS communication protocol.
Look choises of parameter's SW_PB [775] (page 27)
CW_MODBUS [832]
Command Word sent by the Modbus master. For a more detailed description,
see the documentation for MODBUS communication protocol.
Look choises of parameter's CW_PB [776] (page 27)