Name
[ID]
Description
Def.
and X1:12 in the 2 to 10V(~0 až 100%) DC range. If this voltage drops under the 2V limit, the
inverter generates the fault " E25-Interrupted AIN1 (page 33)". Fault evaluation can be turned off
using AIN Fault [790] (page 73).
0-20mA
Analog input level corresponds with the current, which is measured between the terminals X1:11
and X1:12 in the 0 to 20mA(~0 až 100%) range.
4-20mA
Analog input level corresponds with the current, which is measured between the terminals X1:11
and X1:12 in the 4 to 20mA(~0 až 100%) range. If this voltage drops under the 4 mA limit, the
inverter generates the fault " E25-Interrupted AIN1 (page 33)". Fault evaluation can be turned off
using AIN Fault [790] (page 73).
AIN1
Filter
[334]
Time constant of first-order filter of the analog input.
1 ms
0 ms ÷
30000
ms
SPECIAL SETTING AIN1
Group of parameters number [569]
Analog input mapping setting for the selected parameter. Value of this parameter will be affected by the
analog input value.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG INPUTS \ AIN1 \ SPECIAL SETTING AIN1
Name [ID]
Description
Def.
AIN1 Signal [331]
Selection of the signal that will be linearly recalculated according to the analog
input.
-
Signal
Signal
(AIN1_A)
[332]
Signal value for the analog input level in point A.
-
- ÷ -
Signal
(AIN1_B)
[333]
Signal value for the analog input level in point B.
-
- ÷ -
AIN1_A [97]
Analog input level in point A.
0.00 V
0.00 V ÷ 10.00 V
AIN1_B [98]
Analog input level in point B.
20.00
V
0.00 V ÷ 10.00 V
AIN2
Group of parameters number [329]
Second analog input.
MENU \ SETTINGS \ INPUTS AND OUTPUTS \ ANALOG INPUTS \ AIN2
Name
[ID]
Description
Def.
AIN2
Type
[336]
Analog input type.
0-10 V
0-10 V
Analog input value corresponds with the voltage, which is measured between the terminals X1:13
and X1:14 in the 0V to 10V DC range.
2-10 V
Analog input value corresponds with the voltage, which is measured between the terminals X1:13
and X1:14 in the 2V to 10V DC range. If this voltage drops under the 2V limit, the inverter
generates the fault " E26-Interrupted AIN2 (page 33)". Fault evaluation can be turned off using AIN
Fault [790] (page 73).
0-20 mA Analog input value corresponds with the current, which is measured between the terminals X1:13