Chapter 3
Maintaining the Netra X4200 M2 Server
31
FIGURE 3-3
Slide Release Latches
3. While pinching the release latches, slowly pull the server forward until the
slide rails latch.
Caution –
The server weighs approximately 40 lb (18 kg). The next step requires
two people to dismount and carry the chassis.
4. From the front of the server, pull the release tabs forward and pull the server
forward until it is free of the rack rails.
The release tabs are located on each rail, about midway on the server.
5. Set the server on a sturdy work surface.
6. Perform antistatic measures.
See
“Performing Antistatic Measures” on page 31
.
Performing Antistatic Measures
1. Prepare an antistatic surface on which to set parts during removal and
installation.
Place ESD-sensitive components such as the printed circuit boards on an
antistatic mat. The following items can be used as an antistatic mat:
■
Antistatic bag used to wrap a Sun replacement part