Chapter 3
Maintaining the Netra X4200 M2 Server
79
Note –
Set the heatsink upside down on a clean, flat surface to prevent the thermal
grease from contaminating other components.
c. Pull the CPU socket lever slightly away from the socket. See
FIGURE 3-56
.
d. Pivot the lever up, into the fully open, vertical position.
FIGURE 3-56
Releasing the CPU Socket Lever
e. Open the hinged plate that covers the CPU until it is in the fully open
position and lift the CPU out of the socket, leaving the lever in the vertical,
open position. See
FIGURE 3-57
.