Chapter 3
Maintaining the Netra X4200 M2 Server
59
2. Disconnect the hard drive fan assembly cable from the power board connector
J5. The connector’s location can also be seen in
FIGURE 3-24
.
FIGURE 3-34
Disconnecting the Hard Drive Fan Assembly Cable
3. Carefully lift the hard drive fan assembly cable from the cable guides.
4. Push the green release button on the center of the hard drive fan bracket, and
pivot the bracket backward (
FIGURE 3-35
).
FIGURE 3-35
Releasing the Hard Drive Fan Bracket
5. Slide the bracket forward and lift the hard drive fan assembly from the chassis