Netra X4200 M2 Server Service Manual • May 2007
Replacing a PCI-X Card
Caution –
The total power consumption of all PCI cards combined is not to exceed
80 watts. The maximum power of any one PCI card is 25 watts.
Removing a PCI-X Card
1. Prepare the server for PCI-X card removal. See:
■
“Powering Off the Server” on page 28
■
“Disconnecting Cables From the Server” on page 29
■
“Removing the Server From the Rack” on page 30
■
“Performing Antistatic Measures” on page 31
■
“Removing the Top Cover” on page 33
2. Identify the PCI-X card to remove, loosen the appropriate securing
screw(
FIGURE 3-63
), and twist the green retention latches away from the card.
FIGURE 3-63
PCI Tray and Location of PCI Card Securing Screws
Note –
The screws are captive and cannot be completely removed from the PCI tray.