118
Netra X4200 M2 Server Service Manual • May 2007
#
servicetool --fru_update=mainboard
<Other Options>=<value>
3. Watch the output from the command and respond to the confirmation prompts
to continue the update and to reboot the server:
Servicetool is going to update the mainboard FRU with product and
chassis information collected from the removed mainboard.
The following preconditions must be true for this to work:
* The new mainboard must be installed.
* The service processor must not have been replaced with
the motherboard.
* The service processor firmware must not have been upgraded
prior to the motherboard replacement; do firmware upgrades
after component swaps!
Do you want to continue (y|n)?
y
Mainboard FRU configuration has been updated.
Updating FRUs...done
[(flash)root@SUNSP00144F3A22D5:~]#
Other Options
Value
--
board_replaced=BOARD
Update FRU information for BOARD after board has
been replaced
--fru_product_part_number
Write a new part number to the FRU.
--fru_product_serial_number
Write a new serial number to the FRU.
--fru_chassis_serial_number
Write a new chassis serial number to the FRU.
--fru_asset_tag
W
rite a new asset tag to the FRU.
Содержание Netra X4200 M2
Страница 10: ...x Netra X4200 M2 Server Service Manual May 2007...
Страница 14: ...xiv Netra X4200 M2 Server Service Manual May 2007...
Страница 24: ...10 Netra X4200 M2 Server Service Manual May 2007...
Страница 46: ...32 Netra X4200 M2 Server Service Manual May 2007 Sun ESD mat part number 250 1088...
Страница 133: ...Chapter 3 Maintaining the Netra X4200 M2 Server 119...
Страница 134: ...120 Netra X4200 M2 Server Service Manual May 2007...
Страница 146: ...130 Netra X4200 M2 Server Service Manual May 2007...
Страница 154: ...138 Netra X4200 M2 Server Service Manual May 2007...
Страница 172: ...156 Netra X4200 M2 Server Service Manual May 2007...