Chapter 3
Maintaining the Netra X4200 M2 Server
51
FIGURE 3-27
Lifting the Mass Storage Assembly From the Chassis
7. Set the mass storage assembly aside on an antistatic mat.
8. Consider your next step:
■
If you removed the mass storage assembly as part of another procedure, return
to that procedure.
■
Otherwise, continue to
“Installing the Mass Storage Assembly” on page 51
.
Installing the Mass Storage Assembly
1. Remove the replacement mass storage assembly from its packaging and place
it on an antistatic mat.
2. Move the cables as far out of the way as possible.
3. Pivot the front of the mass storage assembly down and lower the assembly
into the chassis, sliding it forward (
FIGURE 3-28
).