445796 Rev. A
Page 3 of 6
4-20-95
1468A RS232 Port Module Installation Instructions
III.) Adding 1468A to 1462 or TC1262:
NOTE:
If the 1462/TC1262 is already in use, remove AC power before proceeding with installation of the
module.
CAUTION:
Shock hazard inside Program Time Controller. Remove all power before servicing.
1.)
Remove the cover.
2.)
Remove the Keps nut in the upper left corner of the CPU board mounted on cover.
3.)
Place the 5/8" spacer provided on the exposed stud.
4.)
Place the 1468A Board on the spacer and J2 header. Secure the board in place with the nut which was
removed in step 2.
5.)
Connect field wires to RS232 Port as required. See wiring diagrams provided.
6.)
Reattach cover.
7.)
Connect AC power.
IV.) Adding 1468A to 1463:
NOTE:
If the 1463 is already in use, remove AC power before proceeding with installation of the module.
CAUTION:
Shock hazard inside Program Time Controller. Remove all power before servicing.
1.)
Remove the cover.
2.)
Remove the Keps nut in the upper left corner of the CPU board.
3.)
Place the 5/8" spacer provided on the exposed stud.
4.)
Place the 1468A Board on the spacer and J5 header. Secure the board in place with the nut which was
removed in step 2.
5.)
Connect field wires to RS232 Port as required. See wiring diagrams provided.
6.)
Reattach cover.
7.)
Connect AC power.
RS232 PORT BOARD
P/N 413171
RS232 PORT BOARD mounts on this corner
J2 ON CPU BOARD
SPACER
P/N 444836
#6 KEPS NUT
P/N 18965
1462 /TC1262
COVER ASSEMBLY
Inside View
Installation Diagram for Cat. No. 1468A RS232 Port Module
to Cat. No. 1462 or TC1262 Program Time Controller
firealarmresources.com
Содержание 1460
Страница 2: ...firealarmresources com ...
Страница 8: ...1460 61 INSTRUCTION MANUAL Page 6 firealarmresources com ...
Страница 60: ...1460 61 INSTRUCTION MANUAL Page 58 firealarmresources com ...
Страница 106: ...Page D 6 1460 61 INSTRUCTION MANUAL firealarmresources com ...
Страница 108: ...firealarmresources com ...
Страница 124: ...445796 Rev A Page 6 of 6 4 20 95 1468A RS232 Port Module Installation Instructions firealarmresources com ...