PAGE A-6
*WARNING: THIS ROUTINE ACTU-
ALLY OPERATES THE MASTER
TIME PROGRAMMER'S RELAYS.
ALL FIELD DEVICES SHOULD BE
DISCONNECTED FROM CLOCK
AND SIGNAL CIRCUITS PRIOR TO
RUNNING THIS TEST!
1. PRESS A (MENU)
2. ENTER 3 DIGIT ACCESS
CODE
3. PRESS ENTER
YOU ARE IN THE Main Menu.
4. PRESS C
YOU ARE ASKED IF Outputs
ARE All Off.
5. PRESS 8 (YES)
DIAGNOSTIC ROUTINE OPER-
ATES THE DISPLAY AND
RELAYS.
6. FOLLOW THE INSTRUCTIONS
TO TEST THE KEYPAD
7. YOU ARE RETURNED TO THE
Main Menu.
8. PRESS ESC
YOU ARE RETURNED TO THE
DATE & TIME DISPLAY.
TO RUN THE DIAGNOSTIC
ROUTINE