![SMC Networks LECSB Series Скачать руководство пользователя страница 84](http://html1.mh-extra.com/html/smc-networks/lecsb-series/lecsb-series_operation-manual_1299641084.webp)
3 - 48
3. SIGNALS AND WIRING
3.7 Alarm occurrence timing chart
CAUTION
When an alarm has occurred, remove its cause, make sure that the operation signal
is not being input, ensure safety, and reset the alarm before restarting operation.
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
When an alarm occurs in the driver, the base circuit is shut off and the servo motor is coated to a stop. Switch
off the main circuit power supply in the external sequence. To reset the alarm, switch the control circuit power
supply from off to on, press the " SET " button on the current alarm screen, or turn the reset (RES) from off to
on. However, the alarm cannot be reset unless its cause is removed.
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1s
Brake operation
15 to 60ms (Note 2)
Alarm occurs.
Remove cause of trouble.
Brake operation
Power off
Power on
Valid
Invalid
Main circuit
control circuit
power supply
Base circuit
Dynamic brake
Servo-on
(SON)
Reset
(RES)
Ready
(RD)
Trouble
(ALM)
(Note 1)
50ms or longer
Note 1. Shut off the main circuit power as soon as an alarm occurs.
2. Changes depending on the operating status.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent (AL.32),
overload 1 (AL.50) or overload 2 (AL.51) alarm after its occurrence, without removing its cause, the driver
and servo motor may become faulty due to temperature rise. Securely remove the cause of the alarm and
also allow about 30 minutes for cooling before resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative (AL.30)
alarm after its occurrence, the external regenerative resistor will generate heat, resulting in an accident.
(3) Instantaneous power failure
Undervoltage (AL.10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer, then the power restores.
During the servo-on status, the bus voltage dropped to 200VDC or less for LECSB2
-
□
, 158VDC or less
for LECSB
1-
□
.
(4) In position control mode (incremental)
When an alarm occurs, the home position is lost. When resuming operation after deactivating the alarm,
make a home position return.
Содержание LECSB Series
Страница 1: ...PRODUCT NAME AC Servo Motor Driver MODEL Series LECSB Series Doc no JXC OMT0021 B ...
Страница 17: ...7 App 6 Compliance with the European EC directives App 7 App 7 Conformance with UL C UL standard App 10 ...
Страница 255: ...10 1 10 OUTLINE DRAWINGS 10 OUTLINE DRAWINGS 2 10 1 Driver 2 10 2 Connector 4 ...