4. STARTUP
4.1.2 Wiring check
(1) Power supply system wiring
Before switching on the main circuit and control circuit power supplies, check the following items.
(a) Power supply system wiring
The power supplied to the power input terminals (L
1
, L
2
, L
3
, L
11
, L
21
) of the driver should satisfy the
defined specifications. (Refer to section 1.3.)
(b) Connection of driver and servo motor
1) The servo motor power supply terminals (U, V, W) of the driver match in phase with the power
input terminals (U, V, W) of the servo motor.
M
U
V
W
U
V
W
Servo amplifier
Servo motor
2) The power supplied to the driver should not be connected to the servo motor power supply
terminals (U, V, W). To do so will fail the connected driver and servo motor.
U
V
W
U
V
W
M
Servo amplifier
Servo motor
3) The earth terminal of the servo motor is connected to the PE terminal of the driver.
M
Servo amplifier
Servo motor
4) P1-P2 (For 11k to 22kW, P1-P) should be connected.
P
1
P
2
Servo amplifier
(c) When option and auxiliary equipment are used
1) When regenerative option is used under 3.5kW for 200V class and 2kW for 400V class
The lead between P terminal and D terminal of CNP2 connector should not be connected.
The generative brake option should be connected to P terminal and C terminal.
A twisted cable should be used. (Refer to section 12.2)