12 - 21
12. OPTIONS AND AUXILIARY EQUIPMENT
12.6 No-fuse breakers, fuses, magnetic contactors
Always use one no-fuse breaker and one magnetic contactor with one driver. When using a fuse instead of the
no-fuse breaker, use the one having the specifications given in this section.
Driver
No-fuse breaker
Fuse
(Note 2)
Magnetic
contactor
Current
Voltage
AC
(Note 1)
Class
Current
[A]
Voltage
AC
[V]
Not using power
factor improving
reactor
Using power factor
improving reactor
LECSB
□
-S5
30A frame 5A
30A frame 5A
240V
T
10
300V
S-N10
LECSB2-S7
30A frame 5A
30A frame 5A
10
LECSB1-S7
30A frame 10A
30A frame 10A
15
LECSB2-S8
30A frame 10A
30A frame 5A
15
Note 1. When not using the driver as a UL/CSA Standard compliant product, K5 class fuse can be used.
2. Be sure to use a magnetic contactor with an operation delay time of 80ms or less. The operation delay time is the time interval
between current being applied to the coil until closure of contacts.