Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
96
Operating Instructions, 07/2012, A5E03728167
5.6.3.11
Running the inverter in sleep mode
Functionality
The motor is turned off if demand falls below threshold, and turned on if demand rises above
threshold.
5HTXLUHGUHVSRQVHRIVLPSOHKLEHUQDWLRQVOHHSPRGH
'HPDQG
IUHTXHQF\
2XWSXW
IUHTXHQF\
+LEHUQDWLRQ
+LEHUQDWLRQ
21GHOD\
21GHOD\
2))GHOD\
2))GHOD\
)PLQ
)PLQ
3
3
3
3
Setting parameters
Parameter
Function
Setting
P2365[0...2]
Hibernation enable / disable
This parameter enables or disables the hibernation
functionality.
= 0: Disabled (factory default)
= 1: Enabled
P2366[0...2]
Delay before stopping motor [s]
With hibernation enabled, this parameter defines the delay
before the inverter goes into sleep mode.
Range: 0 ... 254 (factory default: 5)
P2367[0...2]
Delay before starting motor [s]
With hibernation enabled, this parameter defines the delay
before the inverter comes out of sleep mode.
Range: 0 ... 254 (factory default: 2)
P1080[0...2]
Minimum frequency [Hz]
Sets minimum motor frequency at which motor will run
irrespective of frequency setpoint. Value set here is valid both
for clockwise and for anticlockwise rotation.
Range: 0.00 ... 599.00 (factory default: 0.00)
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...