Fault and warning codes
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
237
Fault
Cause
Remedy
F52 (continued)
•
r0949 = 35: Block section size wrong
•
r0949 = 36: RAM size exceeded
•
r0949 = 37: Parameter size wrong
•
r0949 = 38: Device header wrong
•
r0949 = 39: Invalid file pointer
•
r0949 = 40: Scaling block version wrong
•
r0949 = 41: Calibration block version wrong
•
r0949 = 50: Wrong serial number format
•
r0949 = 51: Wrong serial number format start
•
r0949 = 52: Wrong serial number format end
•
r0949 = 53: Wrong serial number format month
•
r0949 = 54: Wrong serial number format day
•
r0949 = 1000 + addr: Inverter read data failed
•
r0949 = 2000 + addr: Inverter write data failed
•
r0949 = 3000 + addr: Inverter read data wrong
time
•
r0949 = 4000 + addr: Inverter write data wrong
time
•
r0949 = 5000 + addr: Inverter read data invalid
•
r0949 = 6000 + addr: Inverter write data invalid
•
Power-cycle inverter
•
Contact service department or change inverter
F60
Asic timeout
Internal communications failure.
Check inverter.
Fault appears sporadically:
Note:
•
r0949 = 0: Hardware reported link fail
•
r0949 = 1: Software reported link fail
•
r0949 = 6: Feedback is not disabled for reading
inverter data
•
r0949 = 7: During inverter download, message
didn't transmit to disable feedback
•
Communication failure due to EMC problems
•
Check - and if necessary - improve EMC
•
Use EMC filter
F61
MMC / SD card parameter
cloning failed
Parameter cloning failed.
•
r0949 = 0: MMC / SD card not
connected or incorrect card type or
the card failed to initialize for
automatic cloning
•
r0949 = 1: Inverter data cannot write
to the card.
•
r0949 = 2: Parameter cloning file not
available
•
r0949 = 0: Use an MMC / SD card with FAT16
or FAT32 format , or fit an MMC / SD card to the
inverter.
•
r0949 = 1: Check the MMC / SD card (e.g., is
the card memory full?) - format the card again to
FAT16 or FAT32.
•
r0949 = 2: Put the correct named file in the
correct directory /USER/SINAMICS/DATA.
•
r0949 = 3: Make sure file is accessible -
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...