Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
164
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Dependency: P1060 and P1061 set up and down ramp times respectively for jogging. Rounding times (P1130 - P1133),
rounding type (P1134) and P2167 will also have influence on the JOG ramp.
P1059[0...2]
JOG frequency left [Hz] 0.00 -
599.00
5.00
U, T
-
DDS
Float 2
While JOG left is selected, this parameter determines the frequency at which the inverter will run.
Dependency: P1060 and P1061 set up and down ramp times respectively for jogging.
P1060[0...2] JOG ramp-up time [s]
0.00 -
650.00
10.00
U, T
-
DDS
Float 2
Sets jog ramp-up time. This is the time used while jogging is active.
Dependency: See also P3350, P3353.
Notice:
Ramp times will be used as follows:
•
P1060 / P1061 : JOG mode is active
•
P1120 / P1121 : Normal mode (ON / OFF) is active
•
P1060 / P1061 : Normal mode (ON / OFF) and P1124 is active
The rounding of P1130 - P1133 also applies to the JOG ramping.
Note:
If the SuperTorque function is enabled, the inverter will initially ramp using the value in P3353.
P1061[0...2] JOG ramp-down time [s] 0.00 -
650.00
10.00
U, T
-
DDS
Float 2
Sets ramp-down time. This is the time used while jogging is active.
Dependency: See also P3350, P3353.
Note:
See P1060
P1070[0...2] CI: Main setpoint
-
1050[0]
T
-
CDS
U32 /
I32
3
Defines source of main setpoint.
P1071[0...2] CI: Main setpoint scaling -
1
T
4000H
CDS
U32 /
I16
3
Defines source of the main setpoint scaling.
P1074[0...2] BI: Disable additional
setpoint
-
0
U, T
-
CDS
U32 /
Bin
3
Disables additional setpoint.
P1075[0...2] CI: Additional setpoint
-
0
T
-
CDS
U32 /
I32
3
Defines source of the additional setpoint (to be added to main setpoint).
P1076[0...2] CI: Additional setpoint
scaling
-
[0] 1 [1] 0
[2] 1
T
4000H
CDS
U32 /
I16
3
Defines source of scaling for additional setpoint (to be added to main setpoint).
r1078
CO: Total frequency
setpoint [Hz]
-
-
-
-
-
Float 3
Displays sum of main and additional setpoints.
r1079
CO: Selected frequency
setpoint [Hz]
-
-
-
-
-
Float 3
Displays selected frequency setpoint. Following frequency setpoints are displayed:
•
r1078 Total frequency setpoint
•
P1058 JOG frequency right
•
P1059 JOG frequency left
Dependency: P1055 (BI: Enable JOG right) or P1056 (BI: Enable JOG left) define command source of JOG right or JOG
left respectively.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...