Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
42
Operating Instructions, 07/2012, A5E03728167
Connection macro Description
Display example
Cn007
External push button with analog setpoint
Cn008
PID control with analog input reference
Cn009
PID control with the fixed value reference
Cn010
USS control
Cn011
MODBUS RTU control
Setting connection macros
M
M
M
M
M
M
OK
OK
0RWRUGDWD
&RQQHFWLRQPDFUR
0LQXVVLJQVLJQLILHVFXUUHQW
VHOHFWHGPDFUR
$SSOLFDWLRQPDFUR
&XUUHQWVHOHFWHGPDFUR
V
&Q[[[
V
V
V
V
!V
V
!V
Connection macro Cn001 - BOP as the only control source
OK
OK
M
M
10V AI 1 AI 2 0V DI 1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1+ DO1-
P+ N-
DO2
0V
0V
0~20mA=
0~50/60Hz
220V
N
)DXOW
5XQQLQJ
6SHHG
Connection macro settings:
Parameter Description
Factory
default
Default for
Cn001
Remarks
P0700[0]
Selection of command source
1
1
BOP
P1000[0]
Selection of frequency
1
1
BOP MOP
P0731[0]
BI: Function of digital output 1
52.3
52.2
Inverter running
P0732[0]
BI: Function of digital output 2
52.7
52.3
Inverter fault active
P0771[0]
CI: Analog output
21
21
Actual frequency
P0810[0]
BI: CDS bit 0 (Hand/Auto)
0
0
Hand mode
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...