Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P1013[0...2] Fixed frequency 13 [Hz] -599.00 -
599.00
0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 13.
Note:
See P1001
P1014[0...2] Fixed frequency 14 [Hz] -599.00 -
599.00
0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 14.
Note:
See P1001
P1015[0...2] Fixed frequency 15 [Hz] -599.00 -
599.00
0.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 15.
Note:
See P1001
P1016[0...2] Fixed frequency mode
1 - 2
1
T
-
DDS
U16
2
Fixed frequencies can be selected in two different modes. P1016 defines the mode.
1
Direct selection
2
Binary selection
Note:
See P1001 for description of how to use fixed frequencies.
P1020[0...2] BI: Fixed frequency
selection Bit 0
-
722.3
T
-
CDS
U32 /
Bin
3
Defines origin of fixed frequency selection.
Dependency: Accessible only if P0701 - P070x = 99 (function of digital inputs = BICO)
P1021[0...2] BI: Fixed frequency
selection Bit 1
-
722.4
T
-
CDS
U32 /
Bin
3
See P1020
P1022[0...2] BI: Fixed frequency
selection Bit 2
-
722.5
T
-
CDS
U32 /
Bin
3
See P1020
P1023[0...2] BI: Fixed frequency
selection Bit 3
-
722.6
T
-
CDS
U32 /
Bin
3
See P1020
r1024
CO: Actual fixed
frequency [Hz]
-
-
-
-
-
Float 3
Displays sum total of selected fixed frequencies.
r1025.0
BO: Fixed frequency
status
-
-
-
-
-
U16
3
Displays the status of fixed frequencies.
Bit
Signal name
1 signal
0 signal
00
Status of FF
Yes
No
P1031[0...2] MOP mode
-
1
U, T
-
DDS
U16
2
MOP mode specification.
Bit
Signal name
1 signal
0 signal
00
Setpoint store active
Yes
No
01
No On-state for MOP necessary
Yes
No
Note:
Defines the operation mode of the motorized potentiometer. See P1040.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...