Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
86
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Setting
P3359[0...2]
Hammer on time [ms]
This parameter sets the time for which the additional boost is
applied for each repetition (must be at least 3 x motor
magnetization time).
Range: 0. ... 1000 (factory default: 300)
P3360[0...2]
Hammer off Time [ms]
This parameter sets the time for which the additional boost is
removed for each repetition (must be at least 3 x motor
magnetization time).
Range: 0. ... 1000 (factory default: 100)
Function diagram
Description:
The hammer start mode is enabled when an ON command is issued, and the following
sequence is performed:
●
Ramp up to P3354 Hz with the boost level specified by P1310, P1311, and P1312
●
Revert boost level to that specified by P1310, P1311, and P1312
●
Revert to "normal" setpoint and allow output to ramp using P1120
3
3
3
3
3
3
3
%RRVW
2XWSXWIUHTXHQF\
+]
6XSHUWRUTXHUDPSWLPH
1RRIKDPPHUF\FOHV
5DPSXSWLPH
WLPH
WLPH