Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
205
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2268
Minimum value for PID
feedback [%]
-200.00 -
200.00
0.00
U, T
-
-
Float 3
Sets lower limit for value of feedback signal.
Notice:
When PID is enabled (P2200 = 1) and the signal drops below this value, the inverter will trip with F221.
Note:
P2268 = 100 % corresponds to 4000 hex.
P2269
Gain applied to PID
feedback
0.00 -
500.00
100.00
U, T
-
-
Float 3
Allows the user to scale the PID feedback as a percentage value. A gain of 100.0 % means that feedback
signal has not changed from its default value.
P2270
PID feedback function
selector
0 - 3
0
U, T
-
-
U16
3
Applies mathematical functions to the PID feedback signal, allowing multiplication of the result by P2269.
0
Disabled
1
Square root (root(x))
2
Square (x*x)
3
Cube (x*x*x)
P2271
PID transducer type
0 - 1
0
U, T
-
-
U16
2
Allows the user to select the transducer type for the PID feedback signal.
0
Disabled
1
Inversion of PID feedback signal
Notice:
It is essential that you select the correct transducer type. If you are unsure whether 0 or 1 is applicable,
you can determine the correct type as follows:
1.
Disable the PID function (P2200 = 0).
2.
Increase the motor frequency while measuring the feedback signal.
3.
If the feedback signal increases with an increase in motor frequency, the PID transducer type should
be 0.
4.
If the feedback signal decreases with an increase in motor frequency the PID transducer type should
be set to 1.
r2272
CO: PID scaled
feedback [%]
-
-
-
-
-
Float 2
Displays PID scaled feedback signal.
Note:
r2272 = 100 % corresponds to 4000 hex.
r2273
CO: PID error [%]
-
-
-
-
-
Float 2
Displays PID error (difference) signal between setpoint and feedback signals.
Note:
r2273 = 100 % corresponds to 4000 hex.
P2274
PID derivative time [s]
0.000 -
60.000
0.000
U, T
-
-
Float 2
Sets PID derivative time.
P2274 = 0: The derivative term does not have any effect (it applies a gain of 1).
P2280
PID proportional gain
0.000 -
65.000
3.000
U, T
-
-
Float 2
Allows user to set proportional gain for PID controller. The PID controller is implemented using the
standard model. For best results, enable both P and I terms.
Dependency: P2280 = 0 (P term of PID = 0): The I term acts on the square of the error signal.
P2285 = 0 (I term of PID = 0): PID controller acts as a P or PD controller respectively.
Note:
If the system is prone to sudden step changes in the feedback signal, P term should normally be set to a
small value (0.5) with a faster I term for optimum performance.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...