Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
144
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
Note:
See P0701. Signals above 4 V are active; signals below 1.6 V are inactive.
P0717
Connection macro
0 - 255
0
C(1)
-
-
U16
1
Selects a given connection macro, which is a set of parameter values for a given set of control
connections. There are a number of connection macros which define basic control connection settings
such as Terminals, BOP, PID with analog setpoint etc.
Note:
Please note that to guarantee correct setting of the Connection macro, the Connection macro number
should only be changed during Setup directly after a parameter reset.
P0719[0...2] Selection of command &
frequency setpoint
0 - 57
0
T
-
CDS
U16
4
Central switch to select control command source for inverter. Switches command and setpoint source
between freely programmable BICO parameters and fixed command / setpoint profiles. Command and
setpoint sources can be changed independently. The tens digit chooses the command source and the
units digit chooses the setpoint source.
0
Cmd = BICO parameter, Setpoint = BICO parameter
1
Cmd = BICO parameter, Setpoint = MOP setpoint
2
Cmd = BICO parameter, Setpoint = Analog setpoint
3
Cmd = BICO parameter, Setpoint = Fixed frequency
4
Cmd = BICO parameter, Setpoint = USS on RS232 (reserved)
5
Cmd = BICO parameter, Setpoint = USS on RS485
7
Cmd = BICO parameter, Setpoint = Analog setpoint 2
40
Cmd = USS on RS232 (reserved), Setpoint = BICO parameter
41
Cmd = USS on RS232 (reserved), Setpoint = MOP setpoint
42
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint
43
Cmd = USS on RS232 (reserved), Setpoint = Fixed frequency
44
Cmd = USS on RS232 (reserved), Setpoint = USS on RS232 (reserved)
45
Cmd = USS on RS232 (reserved), Setpoint = USS on RS485
47
Cmd = USS on RS232 (reserved), Setpoint = Analog setpoint 2
50
Cmd = USS on RS485, Setpoint = BICO parameter
51
Cmd = USS on RS485, Setpoint = MOP setpoint
52
Cmd = USS on RS485, Setpoint = Analog setpoint
53
Cmd = USS on RS485, Setpoint = Fixed frequency
54
Cmd = USS on RS485, Setpoint = USS on RS232 (reserved)
55
Cmd = USS on RS485, Setpoint = USS on RS485
57
Cmd = USS on RS485, Setpoint = Analog setpoint 2
Dependency: P0719 has higher priority than P0700 and P1000.
If set to a value other than 0 (i.e. BICO parameter is not the setpoint source), P0844 / P0848 (first source
of OFF2 / OFF3) are not effective; instead, P0845 / P0849 (second source of OFF2 / OFF3) apply and the
OFF commands are obtained via the particular source defined.
BICO connections made previously remain unchanged.
Notice:
Particularly useful when e.g. changing command source temporarily from P0700 = 2.
Settings in P0719 (contrary to P0700 settings) do not reset the digital inputs (P0701, P0702, ...)
r0720
Number of digital inputs -
-
-
-
-
U16
3
Displays number of digital inputs.
r0722.0...12 CO / BO: Digital input
values
-
-
-
-
-
U16
2
Displays status of digital inputs.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...