Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
159
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
15
USS on RS485 + MOP setpoint
17
Analog setpoint 2 + MOP setpoint
20
No main se Analog setpoint
21
MOP se Analog setpoint
22
Analog se Analog setpoint
23
Fixed fre Analog setpoint
25
USS on RS485 + Analog setpoint
27
Analog setpoint 2 + Analog setpoint
30
No main se Fixed frequency
31
MOP se Fixed frequency
32
Analog se Fixed frequency
33
Fixed fre Fixed frequency
35
USS on RS485 + Fixed frequency
37
Analog setpoint 2 + Fixed frequency
50
No main se USS on RS485
51
MOP se USS on RS485
52
Analog se USS on RS485
53
Fixed fre USS on RS485
55
USS on RS485 + USS on RS485
57
Analog setpoint 2 + USS on RS485
70
No main se Analog setpoint 2
71
MOP se Analog setpoint 2
72
Analog se Analog setpoint 2
73
Fixed fre Analog setpoint 2
75
USS on RS485 + Analog setpoint 2
77
Analog setpoint 2 + Analog setpoint 2
Dependency: Related parameter: P1074 (BI: Disable additional setpoint)
Caution:
Changing this parameter sets (to default) all settings on item selected. These are the following parameters:
P1070, P1071, P1075, P1076
If P1000 = 1 or 1X, and P1032 (inhibit reverse direction of MOP) = 1, then reverse motor direction will be
inhibited.
Note:
RS485 also supports MODBUS protocol as well as USS. All USS options on RS485 are also applicable to
MODBUS.
P1001[0...2] Fixed frequency 1 [Hz]
-599.00 -
599.00
10.00
U, T
-
DDS
Float 2
Defines fixed frequency setpoint 1. There are 2 types of fixed frequencies:
1.
Direct selection (P1016 = 1):
–
In this mode of operation 1 Fixed Frequency selector (P1020...P1023) selects 1 fixed frequency.
–
If several inputs are active together, the selected frequencies are summed. E.g.: FF1 + FF2 + FF3
+ FF4.
2.
Binary coded selection (P1016 = 2):
–
Up to 16 different fixed frequency values can be selected using this method.
Dependency: Select fixed frequency operation (using P1000).
Inverter requires ON command to start in the case of direct selection. Therefore r1025 must be connected
to P0840 to start.
Note:
Fixed frequencies can be selected using the digital inputs.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...