Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
190
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
P2013 = 3
P2013 = 4
P2013 = 127
Master → SINAMICS
22BC 0000 0006
22BC 0000 0000 0006
22BC 0000 0006 0000
SINAMICS → Master
12BC 0000 0006
12BC 0000 0000 0006
12BC 0000 0006
P2014[0...1]
USS / MODBUS
telegram off time [ms]
0 - 65535 2000
T
-
-
U16
3
Index 0 defines a time T_off after which a fault will be generated (F72) if no telegram is received via the
USS / MODBUS channel RS485.
Index 1 defines a time T_off after which a fault will be generated (F71) if no telegram is received via the
USS channel RS232 (reserved).
Index:
[0]
USS / MODBUS on RS485
[1]
USS on RS232 (reserved)
Notice:
By default (time set to 0), no fault is generated (i.e. watchdog disabled).
Note:
The telegram off time will function on RS485 regardless of the protocol set in P2023.
r2018[0...7]
CO: PZD from USS /
MODBUS on RS485
-
-
-
4000H
-
U16
3
Displays process data received via USS / MODBUS on RS485.
67;
/*(
$'5
3.:
3='
%&&
67:
+6:
>@
>@
>@
>@
>@
3='
67:
3='
+6:
3='
3='
67:
67;
/*(
$'5
%&&
PKW
PZD
3URFHVVGDWD
6WDUWRIWH[W
/HQJWK
$GGUHVV
3DUDPHWHU,'YDOXH
3URFHVVGDWD
%ORFNFKHFNFKDUDFWHU
&RQWUROZRUG
0DLQVHWSRLQW
866WHOHJUDP
USS on RS485
3DUDPHWHU
PZD mapping to parameter r2018
3
U
U
U
Index:
[0]
Received word 0
[1]
Received word 1
...
...
[7]
Received word 7
Note:
Restrictions:
•
If the above serial interface controls the inverter (P0700 or P0719) then the 1st control word must be
transferred in the 1st PZD-word.
•
If the setpoint source is selected via P1000 or P0719, then the main setpoint must be transferred in the
2nd PZD-word.
•
When P2012 is greater than or equal to 4 the additional control word (2nd control word) must
transferred in the 4th PZD-word, if the above serial interface controls the inverter (P0700 or P0719).
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...