Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
122
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
21
Warnings / faults / monitoring
22
Technology controller
P0007
Backlight delay time
0 - 2000
0
U, T
-
-
U16
3
Defines time period after which the backlight of the operator panel display turns off if no buttons have been
pressed.
0
Backlight always on
1 - 2000
Number of seconds after which the backlight turns off.
P0010
Commissioning
parameter
0 - 30
0
T
-
-
U16
1
Filters parameters so that only those related to a particular functional group are selected.
0
Ready
1
Quick commissioning
2
Inverter
29
Download
30
Factory setting
Dependency: Reset to 0 for inverter to run.
P0003 (user access level) also determines access to parameters.
Note:
•
P0010 = 1
The inverter can be commissioned very quickly and easily by setting P0010 = 1. After that only the
important parameters (e.g.: P0304, P0305, etc.) are visible. The value of these parameters must be
entered one after the other. The end of quick commissioning and the start of internal calculation will be
done by setting P3900 = 1 - 3. Afterwards parameter P0010 and P3900 will be reset to zero
automatically.
•
P0010 = 2
For service purposes only.
•
P0010 = 30
When resetting the parameters or user default values of inverter P0010 must be set to 30.
Resetting of the parameters will be started by setting parameter P0970 = 1.
The inverter will automatically reset all its parameters to their default settings.
This can prove beneficial if you experience problems during parameter setup and wish to start again.
Resetting of the user default values will be started by setting parameter P0970 = 21.
The inverter will automatically reset all its parameters to the factory default settings.
Duration of factory setting will take about 60 seconds.
P0011
Lock for user-defined
parameter
0 - 65535 0
U, T
-
-
U16
3
See P0013
P0012
Key for user-defined
parameter
0 - 65535 0
U, T
-
-
U16
3
See P0013
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...