Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
r0053.0...15 CO / BO: Active status
word 2
-
-
-
-
-
U16
2
Displays second status word of inverter (in bit format).
Bit
Signal name
1 signal
0 signal
00
DC brake active
Yes
No
01
|f_act| > P2167 (f_off)
Yes
No
02
|f_act| > P1080 (f_min)
Yes
No
03
Act. current |r0068| >= P2170
Yes
No
04
|f_act| > P2155 (f_1)
Yes
No
05
|f_act| <= P2155 (f_1)
Yes
No
06
f_act >= setpoint (f_set)
Yes
No
07
Act. unfilt. Vdc < P2172
Yes
No
08
Act. unfilt. Vdc > P2172
Yes
No
09
Ramping finished
Yes
No
10
PID output r2294 == P2292 (PID_min)
Yes
No
11
PID output r2294 == P2291 (PID_max)
Yes
No
14
Download Data set 0 from OP
Yes
No
15
Download Data set 1 from OP
Yes
No
Notice:
r0053 bit 00 "DC brake active" ==> see P1233
Note:
See r2197 and r2198
r0054.0...15 CO / BO: Active control
word 1
-
-
-
-
-
U16
3
Displays first control word of inverter (in bit format) and can be used to diagnose which commands are
active.
Bit
Signal name
1 signal
0 signal
00
ON / OFF1
Yes
No
01
OFF2: Electrical stop
No
Yes
02
OFF3: Fast stop
No
Yes
03
Pulse enable
Yes
No
04
RFG enable
Yes
No
05
RFG start
Yes
No
06
Setpoint enable
Yes
No
07
Fault acknowledge
Yes
No
08
JOG right
Yes
No
09
JOG left
Yes
No
10
Control from PLC
Yes
No
11
Reverse (setpoint inversion)
Yes
No
13
Motor potentiometer MOP up
Yes
No
14
Motor potentiometer MOP down
Yes
No
15
CDS Bit 0 (Hand / Auto)
Yes
No
Notice:
r0054 is identical to r2036 if USS is selected as command source via P0700 or P0719.
r0055.0...15 CO / BO: Active control
word 2
-
-
-
-
-
U16
3
Displays additional control word of inverter (in bit format) and can be used to diagnose which commands
are active.
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...