Parameter list
7.2 Parameter list
SINAMICS V20 Inverter
130
Operating Instructions, 07/2012, A5E03728167
Parameter
Function
Range
Factory
default
Can be
changed
Scaling
Data
set
Data
type
Acc.
Level
r0085
CO: Actual re-active
current [A]
-
-
-
P2002
-
Float 3
Displays re-active (imaginary part) of motor current.
Dependency: Applies when V/f control is selected in P1300 (control mode); otherwise, the display shows the value zero.
r0086
CO: Actual active current
[A]
-
-
-
P2002
-
Float 3
Displays active (real part) of motor current.
Dependency: See r0085
r0087
CO: Actual power factor -
-
-
-
-
Float 3
Displays the actual power factor.
P0095[0...9] CI: Display PZD signals -
0
T
4000H
-
U32 /
I16
3
Selects source of display for PZD signals.
Index:
[0]
1st PZD signal
[1]
2nd PZD signal
...
...
[9]
10th PZD signal
r0096[0...9]
PZD signals [%]
-
-
-
-
-
Float 3
Displays PZD signals.
Index:
[0]
1st PZD signal
[1]
2nd PZD signal
...
...
[9]
10th PZD signal
Note:
r0096 = 100 % corresponds to 4000 hex.
P0100
Europe / North America 0 - 2
0
C(1)
-
-
U16
1
Determines whether power settings are expressed in [kW] or [hp] (e.g. Rated motor power P0307).
The default settings for the rated motor frequency P0310 and maximum frequency P1082 are set
automatically here, in addition to reference frequency P2000.
0
Europe [kW], motor base frequency is 50 Hz
1
North America [hp], motor base frequency is 60 Hz
2
North America [kW], motor base frequency is 60 Hz
Dependency: Where:
•
Stop inverter first (i.e. disable all pulses) before you change this parameter.
•
P0100 can only be changed with P0010 = 1 (Commissioning mode) via the respective interface.
•
Changing P0100 resets all rated motor parameters as well as other parameters that depend on the
rated motor parameters (see P0340 - calculation of motor parameters).
P0199
Equipment system
number
0 - 255
0
U, T
-
-
U16
4
Equipment system number. This parameter has no operation effect (only for factory purposes).
r0206
Rated inverter power
[kW] / [hp]
-
-
-
-
-
Float 2
Displays nominal rated motor power from inverter.
Dependency: Value is displayed in [kW] or [hp] depending on setting for P0100 (operation for Europe / North America).
r0207[0...2]
Rated inverter current [A] -
-
-
-
-
Float 2
Displays rated inverter current.
Index:
[0]
Rated inverter current
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...