Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
48
Operating Instructions, 07/2012, A5E03728167
Parameter
Description
Factory
default
Default for
Cn006
Remarks
P0732[0]
BI: Function of digital output 2
52.7
52.3
Inverter fault active
P1040[0]
Setpoint of the MOP
5
0
Initial frequency
P1047[0]
MOP ramp-up time of the RFG
10
10
Ramp-up time from zero to
maximum frequency
P1048[0]
MOP ramp-down time of the RFG
10
10
Ramp-down time from maximum
frequency to zero
Connection macro Cn007 - External push buttons with analog control
Note that the command sources are pulse signals.
OK
OK
M
M
10V AI 1 AI 2 0V DI 1 DI2 DI3 DI4 DIC 24V 0V
AO + AO- DO1+ DO1-
P+ N-
DO2
0V
0V
0~20mA=
0~50/60Hz
220V
0~10V=
0~50/60Hz
N
2))KROG
)RUZDUGSXOVH21
5HYHUVHSXOVH21
)DXOWDFNQRZOHGJHPHQWSXOVH
)DXOW
5XQQLQJ
6SHHG
2))
)RUZDUG
5HYHUVH
Connection macro settings:
Parameter
Description
Factory
default
Default for
Cn007
Remarks
P0700[0]
Selection of command source
1
2
Terminals as command source
P1000[0]
Selection of frequency
1
2
Analog
P0701[0]
Function of digital input 1
0
1
OFF hold
P0702[0]
Function of digital input 2
0
2
Forward pulse + ON
P0703[0]
Function of digital input 3
9
12
Reverse pulse + ON
P0704[0]
Function of digital input 4
15
9
Fault acknowledgement
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...