Commissioning
5.6 Function commissioning
SINAMICS V20 Inverter
Operating Instructions, 07/2012, A5E03728167
91
5.6.3.6
Setting the free function blocks (FFBs)
Functionality
Additional signal interconnections in the inverter can be established by means of free
function blocks (FFBs). Every digital and analog signal available via BICO technology can be
routed to the appropriate inputs of the free function blocks. The outputs of the free function
blocks are also interconnected to other functions using BICO technology.
Example
%LW
U ',
'2
',
',
',
',
',
', ',
U $1'
U
U
U
3
3
>@
>@
Setting parameters
Parameter
Function
Setting
P0702
Function of digital input 2
= 99: Enable BICO parameterization for digital input 2
P0703
Function of digital input 3
= 99: Enable BICO parameterization for digital input 3
P2800
Enable FFBs
= 1: Enable (general enable for all free function blocks)
P2801[0]
Activate FFBs
= 1: Enable AND 1
P2810[0]
= 722.1
P2810[1]
BI: AND 1
= 722.2
P2810[0] and P2810[1] define inputs of AND 1
element, and output is r2811.0.
P0731
BI: Function of digital output 1
This parameter defines source of digital output 1.
= r2811.0: Use the AND (DI2, DI3) to switch on LED
For more information about FFBs and additional settings of individual parameter, see
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...