Commissioning
5.5 Quick commissioning
SINAMICS V20 Inverter
40
Operating Instructions, 07/2012, A5E03728167
5.5.1.2
Setting motor data
Functionality
This menu is designed for easy setup of nominal motor nameplate data.
Text menu
If you set P8553 to 1, parameter numbers in this menu are replaced with short text.
Setting parameters
NOTICE
In the table below, "●" indicates that the value of this parameter must be entered according
to the rating plate of the motor.
Parameter
Access
level
Function
Text menu
(if P8553 = 1)
P0100
1
50 / 60 Hz selection
=0: Europe [kW], 50 Hz (factory default)
=1: North America [hp], 60 Hz
=2: North America [kW], 60 Hz
(EU - US)
P0304[0] ●
1
Rated motor voltage [V]
Note that the input of rating plate data must correspond with the
wiring of the motor (star / delta)
(MOT V)
P0305[0] ●
1
Rated motor current [A]
Note that the input of rating plate data must correspond with the
wiring of the motor (star / delta)
(MOT A)
P0100 = 0 or 2:
(MOT P)
P0307[0] ●
1
Rated motor power [kW / hp]
If P0100 = 0 or 2, motor power unit = [kW]
If P0100 = 1, motor power unit = [hp]
P0100 =1:
(MOT HP)
P0308[0] ●
1
Rated motor power factor (cosφ)
Visible only when P0100 = 0 or 2
(M COS)
P0309[0] ●
1
Rated motor efficiency [%]
Visible only when P0100 = 1
Setting 0 causes internal calculation of value.
(M EFF)
P0310[0] ●
1
Rated motor frequency [Hz]
(M FREQ)
Содержание SINAMICS V20 Series
Страница 4: ...Preface SINAMICS V20 Inverter 4 Operating Instructions 07 2012 A5E03728167 ...
Страница 12: ...Safety instructions SINAMICS V20 Inverter 12 Operating Instructions 07 2012 A5E03728167 ...
Страница 232: ...Parameter list 7 2 Parameter list SINAMICS V20 Inverter 232 Operating Instructions 07 2012 A5E03728167 ...
Страница 274: ...Index SINAMICS V20 Inverter 274 Operating Instructions 07 2012 A5E03728167 ...